Always-on remote tools and LTE modems left by equipment vendors are among the most common ways around network segmentation. This guide covers how to design OT remote maintenance control, from inventorying access paths to request-approve-connect-close workflows, session recording, and PLC change comparison.

POLYGLOTSOFT Tech Team2026-11-097 min read7
OT SecurityRemote MaintenanceEquipment SecurityAccess ControlSmart Factory

The Gap in Factory Security Is Vendor Remote Access

Most plants put up firewalls and separate the office network from the production network. Yet the remote paths equipment vendors use often fall outside that perimeter. To respond quickly to breakdowns, vendors routinely install remote control software on HMI PCs or mount an LTE modem inside the control cabinet and leave it connected around the clock.

The problem is that these paths leave almost no trail. The plant cannot tell who logged in, when, to which machine, or whether they changed the PLC logic. However well the networks are segmented, a single LTE modem becomes a separate internet doorway that never passes through the firewall. If the vendor's laptop is compromised, that doorway becomes an attack path.

Start With a Full Inventory of Remote Access Paths

You cannot control what you have not found.

  • List every access method: remote desktop tools, vendor VPNs, built-in modems, and manufacturer cloud portals, machine by machine
  • Separate always-on from on-demand: check whether the software runs constantly or is only started when needed
  • Map vendor, account, and owner: for each path, record which vendor and account it belongs to and who on the plant side is responsible
  • Check for shared accounts and default passwords: find accounts passed around among a vendor's technicians and credentials never changed since shipment
  • On a line of around 50 machines, it is not unusual for this inventory alone to turn up several paths the plant did not know about. Modems inside cabinets are often missing from drawings, so a physical walkdown is needed.

    Move to a Request–Approve–Connect–Close Flow

    The core idea is to turn an always-open door into one that opens only on request.

  • The vendor submits a request listing the target machine, the work, and the expected duration
  • The equipment owner checks the production schedule and approves it
  • Access is allowed only for the approved window (for example, two hours)
  • When the work ends or the window expires, access is cut off automatically
  • Consolidate all paths through a single remote access gateway (jump server). Vendors reach the gateway and nothing else; from there they connect only to approved machines. This fits the zone-and-conduit model described in IEC 62443. Issue individual accounts per vendor technician, enforce multi-factor authentication, and restrict each account to a defined set of machines.

    What to Capture During a Session

  • Session recording: record the screen so incidents can be replayed
  • Command and file transfer logs: track which files came in and went out
  • Before-and-after PLC comparison: back up the program before and after each session and diff it automatically
  • Write operations on running equipment need separate handling. Allow read-only monitoring remotely, but tie logic downloads and parameter changes to on-site supervision or a stopped production state. Remote access history should feed into your existing PLC change management and backup system, so "who logged in and what changed" lives in one place.

    Rolling It Out in Stages

    Changing everything at once invites pushback from the floor. A three-stage rollout works better.

  • Stage 1: inventory paths, cut always-on connections, clean up shared accounts and default passwords
  • Stage 2: consolidate on a gateway, introduce individual accounts and MFA
  • Stage 3: automate the approval workflow, session recording, and change comparison
  • Write remote access conditions, mandatory gateway use, and log delivery obligations into vendor contracts. Answer the operators' fear that "the line will sit idle while we wait for approval" with an emergency procedure: the night-shift lead approves immediately after a phone check, and the work is reviewed afterward. Emergency sessions are recorded and logged just like any other.

    How POLYGLOTSOFT Helps

    POLYGLOTSOFT builds remote access request and approval workflows linked to the equipment master in your MES. Approvers are assigned automatically based on machine ownership and production status, and a dashboard ties access history to PLC change history. If you want to bring vendor remote access under control without slowing down breakdown response, talk to POLYGLOTSOFT.